3-42
|
Chapter 3 Configuration
XX200-00
Pilot Plus
Field Description
Pattern
Select up to three patterns for the alarm action: A, B
or C. Each can have a different action.
Note:
Upon startup, the system will default to
pattern A.
Closure Type
Use this field to set closure type to Normally Open,
where alarm activates when the alarm contacts
close (Make) or Normally Closed, where alarm
activates when the alarm contacts open (Break).
Note:
Normally open and normally closed closure
types refer to the X-IA state and do not refer to the
RS-232 port or receiver alarm state.
Alarm Enable
Used to enable or disable alarm input action for
pattern A, B or C.
Momentary/Latching Used to set the alarm as a momentary or latching
type. A momentary alarm remains active only as
long as the alarm switch contacts are in the position
that defines an alarm. For example, some alarms
are activated when the contacts close and others
when the contacts open. If a normally closed
momentary alarm is connected to a door, the alarm
is active only while the door is open. Latching
alarms remain in their current state, for example, a
latching normally closed door alarm will activate
when the door is opened and remain active until the
alarm is acknowledged. The default state of X-IA
alarms is latching.
You can use the patterns field to set X-IA alarms as
momentary or latching at different times. For
example, Pattern A might set an X-IA alarm to act
as momentary during the day, while pattern B sets
all X-IA alarms to act as latching at night.
All selections are made using the Options Wizard. To change a field’s value,
proceed as follows:
1. Select the field that you wish to modify using the Available Field
selection box. You can scroll through all available options.
2. Upon selection, the title below Available Field will change to the
parameter selected and the appropriate values will display in the
selection box.