Bit
Signal name
Remark
2
POS
Positioning mode (POS)
A set position is specified by the higher-level control system or the target generator. In
this mode, the hoist travels to this position.
0: Not active
1: Active
3
MAN
Manual mode (MAN)
The higher-level control system specifies a set velocity.
0: Not active
1: Active
4
-
Reserved
5
-
Reserved
6
SAM
Semi-automatic mode (SAM)
If the trolley and the hoist are in this operating mode and target positions are specified
for both drives, a calculated trajectory will be traveled.
0: Not active
1: Active
7
-
Reserved
8
LS_UP
Limit switch up
0: Operated
1: Not operated
9
LS_DN
Limit switch down
0: Operated
1: Not operated
10
PRELS_UP
Prelimit switch up
This bit is active only when P115 = 0. Otherwise the dynamic prelimit switch will be used.
0: Operated
1: Not operated
11
PRELS_DN
Prelimit switch down
This bit is active only when P115 = 0. Otherwise the dynamic prelimit switch will be used.
0: Operated
1: Not operated
12
BRAKE_CLOSED
Output value enable
0: Output value and direction signals are set.
1: Output value is not enabled (braking with maximum deceleration); direction signals
are set.
13-15
-
Reserved
Communication interface to SIMATIC S7
4.1 SIMATIC S7 → SIMOTION D for AddOn
SC integrated STS, GSU
Operating Instructions, 07/2019, A5E48271265B AA
87