9.6.2
Commissioning cylinders
Perform the following steps:
1. Activating the TLS functions
Set the following parameters for activation of the TLS functions:
– P240=1
– P320=1
– P321=0
2. See Chapter Parameterization of the actual positions (Page 351)
3. See Chapter Parameterizing "cylinder jogging" mode (Page 352)
4. See Chapter Parameterization of the central positions of the cylinders (Page 354)
5. See Chapter TLS inching and go to zero positions (Page 356)
6. See Chapter Conversion of cylinder positions, angle of rotation (Page 357)
9.6.3
Evaluation of the current position of the skew drive spindle
The current position of the spindle is available at input RPOS_SKEWAXIS of the DCC block.
This value is "raw" without a defined unit. It is converted to mm by the following method:
● s_act_SkA = P322 · RPOS_SK P323
(P322 = position conversion factor for skew drive)
(P323 = position conversion offset for skew drive)
Please note:
● The factor must be set such that a value in mm is obtained with s_act_SkA.
● The actual values must have a sufficiently high resolution to support position control of the
skew axis. A resolution of approximately 1 mm/increment has proven satisfactory in
practice.
● The offset must be set such that the skew drive spindle is in the zero position (see figure
below) when s_act_SkA = 0 mm.