During travel: The actual position has violated a fixed or variable blocked region. The course
has deviated too far from the setpoint.
Error type:
Error
Remedy:
If necessary, move out of the fixed blocked region (e.g. sill beam zone)
manually, increase safety clearances P33, P72, increase control re‐
serve, reduced gain factors, increase position controller
E38 (Bit 25) Target in fixed blocked region
SAM mode only
The target position is in a fixed blocked region. No direction signals are set.
Error type:
Error
Remedy:
Check the target position and the fixed blocked region
E41 (Bit 29) Trolley following error
The difference between the actual and the delayed output position is greater than the set
permissible following error (P161)
Error type:
Error
Remedy:
● Check the current position of the trolley (rS_Act_TR)
● Check the current velocity of the trolley (rV_Pos_TR)
● Increase the value of P161
● Optimize the controllers
E42 (Bit 30) Hoist following error
The difference between the actual and the set position is greater than the set permissible
following error (P164)
Error type:
Error
Remedy:
● Check the current position of the hoist (rS_Act_HO)
● Check the current velocity of the hoist (rV_Pos_HO)
● Increase the value of P164
● Optimize the controllers
Alarm, error, and system messages
10.5 Error messages