
End of a cylinder movement
PRGHBFRPP
PRYH
DBRXWBFRPP
DBRXW
,1
PRWLRQBWHUPLQDWHG
%63(('B$B1250
,1
,1
287
287
287
Figure 7-6
Signal sequence for ending a cylinder movement in "cylinder jogging" mode
Section 1
Cylinder A is extended according to its output velocity.
Section 2
● Reset the "a_out_comm" control bit (STW2_PLC_TLS, bit 4).
● Depending on the control selected in STW2_PLC_TLS, the status bits 8 ... 15 change to
"false".
In this example: Status bit "a_out" (ZSW1_TLS_PLC, bit 8)
● The output velocity of cylinder A specified by "BSPEED_A_NORM" is reduced to zero.
Section 3
● The status bit "motion_terminated" (ZSW1_TLS_PLC, bit 3) changes to "true" when the
cylinder stops moving.
● Deactivate the move command by resetting the "move" control bit (STW1_PLC_TLS, bit 5).
● Terminate "cylinder jogging" mode by resetting the "mode_comm" control bit
(STW1_PLC_TLS, bit 6).
7.2.2
"Go to zero positions" mode
Go to zero positions
The cylinders move to their zero positions when the relevant "move_zero" control bit is set.
When they have reached their zero positions, the zero status bit is set.
TLS control function description
7.2 TLS modes and TLS functions
SC integrated STS, GSU
Operating Instructions, 07/2019, A5E48271265B AA
243