Error E58 is triggered in the following cases:
● The trolley is moving at a velocity of >20% (reference value is P0) forward or backward.
● The hoist is moving at a velocity of >3% (reference value is P40) in the lowering direction.
A movement in the hoisting direction does not result in an error message.
Note
Monitoring is triggered if either the actual velocity or the output velocity exceeds the stated
threshold values.
Applies to trolley and hoist
Note
The error is only triggered in the following cases when the specified threshold values are
exceeded:
● The mode of the trolley and hoist changes from MAN to SAM (edge evaluation).
● At the time of mode switchover, the TRAVEL control bit is set for both drives.
6.12
Selection of the control method
6.12.1
Selection
Two control methods are available:
● Conventional control
● Time-optimized control
The control method is selected via parameter P152.
6.12.2
Conventional control
Use of the conventional control method produces an aperiodic characteristic for the sway
angle. The acceleration ramp is smoothed. The acceleration times equal approximately 1.1
times the natural oscillation duration of the load oscillation.
The travel operations place very low mechanical stress on the crane structure. The travel
behavior is smooth and comfortable for the crane driver.
Precise positioning is possible.
Sway Control function description
6.12 Selection of the control method
SC integrated STS, GSU
Operating Instructions, 07/2019, A5E48271265B AA
193