Appendix
A.4 Technology alarms
S7-1500 Motion Control V13 Update 3
382
Function Manual, 07/2014, A5E03879256-AC
Technology alarm 504
Alarm reaction: No reaction
Restart: Not required
Alarm text
Solution
Speed setpoint monitoring active.
Check the mechanical configuration.
Check the encoder connection.
Check the configuration of the speed setpoint interface.
Check the configuration of the control loop.
Check the value for the maximum speed
DynamicLimits.MaxVelocity.
Enter a value ≤ Actor.MaxSpe
ed for the "Velocity"
parameter at the Motion Control instruction.
Technology alarm 521
Alarm reaction: Remove enable
Restart: Not required
Alarm text
Solution
Window of the following error monitoring exceeded.
Check the configuration of the control loop.
Check the direction of the encoder.
Check configuration of the following error monitoring.
Technology alarm 522
Alarm reaction: No reaction
Restart: Not required
Alarm text
Solution
Warning level of the following error monitoring exceeded
Check the configuration of the control loop.
Check the direction of the encoder.
Check configuration of the following error monitoring.