Appendix
A.2 Tags of the positioning axis/synchronous axis technology object
S7-1500 Motion Control V13 Update 3
Function Manual, 07/2014, A5E03879256-AC
355
A.2.26
ErrorDetail tags (positioning axis/synchronous axis)
The tag structure <TO>.ErrorDetail.<tag name> contains the alarm number and the effective
local alarm reaction to the technology alarm that is currently pending at the technology
object.
A list of the technology alarms and alarm reactions can be found in the appendix,
Technology Alarms (Page 368).
Tags
Tag
Data type Values
W
Description
ErrorDetail.
STRUCT
Number
UDINT
-
RON Alarm number
Reaction
DINT
0 to 5
RON Effective alarm reaction
0: No reaction
1: Stop with current dynamic values
2 Stop with maximum dynamic values
3: Stop with emergency stop ramp
4: Remove enable
5: Follow-up setpoints
For the external encoder technology object, only
alarm reactions 0 and 4 are possible.
See also
Evaluating the technology data block (Page 173)
Technology alarms (Page 215)