Appendix
A.4 Technology alarms
S7-1500 Motion Control V13 Update 3
Function Manual, 07/2014, A5E03879256-AC
369
No.
Response
Error bit
Warning bit
Restart
Alarm text
204 Remove enable
X0 (SystemFault) -
-
Commissioning error.
304 Stop with emergency
stop ramp
X2 (UserFault)
-
-
Limit value for velocity is zero.
305 Stop with emergency
stop ramp
X2 (UserFault)
-
-
Limit value for acceleration/deceleration
is zero.
306 Stop with emergency
stop ramp
X2 (UserFault)
-
-
Limit value for jerk is zero.
307 Stop with maximum
dynamic values
X2 (UserFault)
-
-
The numeric value range of the position
was reached.
308 Remove enable
X2 (UserFault)
-
-
The numeric value range of the position
was exceeded.
321 Stop with emergency
stop ramp
X3 (Command-
NotAccepted)
-
-
Axis is not homed.
322 No reaction
-
X3 (Command-
NotAccepted)
-
Restart not performed.
323 No reaction
-
X3 (Command-
NotAccepted)
-
MC_Home was not executed because
this would result in the numerical value
range being exceeded.
341 Remove enable
X10 (HomingFault) -
-
Error in homing data.
342 Stop with emergency
stop ramp
X10 (HomingFault) -
-
Reference cam / encoder zero mark was
not found.
401 Remove enable
X13 (Peripheral
Error)
-
-
Error accessing logical address.
411 Remove enable
X5 (SensorFault)
-
-
Encoder at the logical address disrupted.
412 Remove enable
X5 (SensorFault)
-
-
Violation of the range limit for the incre-
mental actual value.
421 Remove enable
X4 (DriveFault)
-
-
Drive/actuator at the logical address
disrupted.
431 Remove enable
X7
(Communication-
Fault)
-
-
Communication with device disrupted.
501 No reaction
-
X6
(DynamicError)
-
Programmed velocity limited.
502 No reaction
-
X6
(DynamicError)
-
Programmed acceleration/deceleration
limited.
503 No reaction
-
X6
(DynamicError)
-
Programmed jerk limited.
504 No reaction
-
X6
(DynamicError)
-
Speed setpoint monitoring active.
521 Remove enable
X11 (Following
ErrorFault)
-
-
Window of the following error monitoring
exceeded.
522 No reaction
X11 (Following-
ErrorWarning)
Warning level of the following error moni-
toring exceeded