Appendix
A.4 Technology alarms
S7-1500 Motion Control V13 Update 3
Function Manual, 07/2014, A5E03879256-AC
379
A.4.5
Technology alarms 401-431
Technology alarm 401
Alarm reaction: Remove enable
Restart: Not required
Alarm text
Solution
Error accessing logical address.
The requested logical address is invalid.
Connect a suitable device. Check the device (I/Os).
Check the topological configuration in HW Config.
Compare the configuration in HW Config and the tech-
nology object.
The requested logical output address is invalid.
The requested logical output address is invalid.
Technology alarm 411
Alarm reaction: Remove enable
Restart: Not required
Alarm text
Solution
Encoder at the logical address disrupted.
Alarm message from encoder.
Check the device in regard to function, connections and
I/Os.
General hardware error of the encoder.
Encoder dirty.
Error reading the absolute value of the encoder.
Compare the encoder type in the drive or encoder pa-
rameter P979 with the configuration data of the technol-
ogy object.
Zero mark monitoring of the encoder.
Encoder reports error for the zero mark monitoring (error
code 0x0002 in Gx_XIST2, see PROFIDrive profile).
Check the system for electromagnetic compatibility
(EMC).
Encoder has gone in parking state.
Locate the cause of the error in the connected drive or
encoder. Check whether the alarm was possibly trig-
gered by a startup action on the drive or encoder.