Diagnostics
10.3 Technology alarms
S7-1500 Motion Control V13 Update 3
218
Function Manual, 07/2014, A5E03879256-AC
Acknowledging technology alarms
You can acknowledge technology alarms as follows:
●
TIA Portal
–
"Technology object > Diagnostics > Status and error bits"
Click "Confirm" to acknowledge all alarms and warnings pending for the selected
technology object.
(Not possible for external encoder technology object)
–
"Technology object > Commissioning > Axis control panel"
Click "Confirm" to acknowledge all alarms and warnings pending for the selected
technology object.
(Not possible for external encoder technology object)
–
"Inspector window > Diagnostics > Message display"
You can acknowledge the alarms and warnings for all technology objects either
individually, or all at once.
●
HMI
At an HMI with enabled message display, you can acknowledge the alarms and warnings
for all technology objects either individually, or all at once.
●
User program
Acknowledge pending alarms at a technology object using the Motion Control instruction
"MC_Reset".
Additional information
A list of the technology alarms and alarm reactions can be found in the appendix,
Technology Alarms (Page 368).