Instructions
11.1 S7-1500 Motion Control V2
S7-1500 Motion Control V13 Update 3
Function Manual, 07/2014, A5E03879256-AC
271
Requirements
●
The technology object has been configured correctly.
●
The leading axis is a positioning axis or synchronous axis.
●
The following axis is a synchronous axis.
●
The leading axis is specified as possible leading axis in the configuration of the following
axis in "Technology object > Configuration > Master value interconnections".
●
The following axis is enabled.
Override response
The "MC_GearIn" job is aborted by:
●
Disabling the following axis with "MC_Power.Enable" = FALSE
●
"MC_Home" job "Mode" = 3, 5
●
"MC_Halt" job
●
"MC_MoveAbsolute" job
●
"MC_MoveRelative" job
●
"MC_MoveVelocity" job
●
"MC_MoveJog" job
●
"MC_GearIn" job
Starting a "MC_GearIn" job aborts the following active Motion Control jobs:
●
"MC_Home" job "Mode" = 3, 5
●
"MC_Halt" job
●
"MC_MoveAbsolute" job
●
"MC_MoveRelative" job
●
"MC_MoveVelocity" job
●
"MC_MoveJog" job
●
"MC_GearIn" job
Disabling the leading axis with "MC_Power.Enable" = FALSE does not abort synchronous
operation. The following axis follows the leading axis even during the braking ramp and after
the leading axis is enabled again.