[lo_GPP operate indication logical comb, 2, en_US]
Figure 7-170
Logical Combination of Operate Indications in CFC
Active Power Stage
Logic of a Stage
[lo_3-phase active power, 2, en_US]
Figure 7-171
Logic Diagram of the Active Power Stage (Stage Type: Power P<)
Measured Value
The
Measured value
parameter is used to specify which measured power value is analyzed by the tripping
stage. Possible settings are
positive seq. power
and the phase-selective powers
power of phase A
,
power of phase B
or
power of phase C
.
Pickup Characteristic
With the stage type you specify if the stage work as a greater stage (stage type: Power P>) or as a smaller
stage (stage type: Power P<).
7.22.3
Protection and Automation Functions
7.22 Power Protection (P,Q), 3-Phase
SIPROTEC 5, High-Voltage Bay Controller, Manual
853
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...