The setting value for the
Time dial
parameter is derived from the time-grading chart that has been
prepared for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the param-
eter
Time dial
at 1 (default setting).
Settings
Addr.
Parameter
C
Setting Options
Default Setting
V-dependent 1
_:11491:1
V-dependent 1:Mode
•
off
•
on
•
test
off
_:11491:2
V-dependent 1:Operate
& flt.rec. blocked
•
no
•
yes
no
_:11491:27
V-dependent 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:11491:8
V-dependent 1:Method
of measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:11491:3
V-dependent
1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:11491:101
V-dependent 1:Type of
character. curve
_:11491:102
V-dependent 1:Reset
•
instantaneous
•
disk emulation
disk emulation
_:11491:103
V-dependent 1:Time dial
0.05 to 15.00
1.00
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
V-dependent 1
_:11491:81
V-dependent 1:>Block stage
SPS
I
_:11491:500
V-dependent 1:>Block delay & op.
SPS
I
_:11491:54
V-dependent 1:Inactive
SPS
O
_:11491:52
V-dependent 1:Behavior
ENS
O
_:11491:53
V-dependent 1:Health
ENS
O
_:11491:60
V-dependent 1:Inrush blocks operate
ACT
O
_:11491:59
V-dependent 1:Disk emulation running
SPS
O
_:11491:55
V-dependent 1:Pickup
ACD
O
_:11491:56
V-dependent 1:Operate delay expired
ACT
O
_:11491:57
V-dependent 1:Operate
ACT
O
7.12.3.3
7.12.3.4
Protection and Automation Functions
7.12 Voltage-Dependent Overcurrent Protection
SIPROTEC 5, High-Voltage Bay Controller, Manual
779
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...