
You can switchover the settings groups via the following alternatives:
•
Via the on-site operation panel directly on the device
•
Via an online DIGSI connection to the device
•
Via binary inputs
•
Via a communication connection to substation automation technology (IEC 60870-5-103, IEC 61850)
You can find more information in chapter
3.10.1 Settings-Group Switching
.
Control Response
Control Deviation
The control deviation is calculated from the present actual voltage and the target voltage in relation to the
rated voltage.
[fokonisk-211013, 2, en_US]
D = Control deviation
Bandwidth
To minimize the number of switching operations by the tap changer, a permitted bandwidth is defined. If the
actual voltage is within the bandwidth, no adjusting control commands are issued to the tap changer. If the
actual voltage exceeds the defined bandwidth, an adjusting command is issued after the set time delay
T1
delay
. If the actual voltage returns to the voltage range of the bandwidth before
T1 delay
elapses, no
adjusting control command is issued.
If the actual voltage returns to the voltage range of the bandwidth within the time delay T1, the running time
delay T1 continues to count down, starting at the already elapsed time. If the actual voltage returns again to
the set bandwidth while the time is counting down, the time delay T1 is started at the remaining time. In this
way, the time delay is reduced in the event of frequent violations of the lower limit of the bandwidth.
[dwistspn-060913-01.vsd, 1, en_US]
Figure 6-124
Actual-Voltage Curve during Control Deviation
(a)
Actual voltage outside the bandwidth
(b)
Actual voltage before T1 elapses within the bandwidth - no switching
(c)
Actual voltage outside the bandwidth, T1 begins to elapse
6.9.3.3
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
459
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...