Device Settings
Settings-Group Switching
Overview of Functions
For different applications you can save the respective function settings in so-called Settings groups, and if
necessary enable them quickly.
You can save up to 8 different settings groups in the device. In the process, only one settings group is active at
any given time. During operation, you can switch between settings groups. The source of the switchover can
be selected via a parameter.
You can switchover the settings groups via the following alternatives:
•
Via the on-site operation panel directly on the device
•
Via an online DIGSI connection to the device
•
Via binary inputs
•
Via a communication connection to the substation automation technology.
The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC 61850, DNP or Modbus TCP can be
used for switching the settings groups.
A settings group includes all switchable settings of the device. Except for a few exceptions (for example,
general device settings such as rated frequency), all device settings can be switched.
Detailed information about the settings groups can be found in the Operating Manual and DIGSI 5 Online
Help.
Structure of the Function
The function of the Settings group switching is a supervisory device function. Accordingly, the settings and
indications of the settings group switching can be found in DIGSI 5 and at the on-site operation panel of the
device, below the general device settings respectively.
If you want to switchover a settings group, navigate to DIGSI 5 or proceed on the on-site operation panel of
the device, as follows:
•
Via the project tree in DIGSI 5:
Project -> Device -> Settings -> Device settings
•
Via the on-site operation panel of the device:
Main menu → Settings → General → Group switchover
The indications for the settings group switching can be found in the DIGSI 5 project tree under:
Project → Device → Information routing → General
Function Description
Activation
If you want to use the Settings group switching function, you must first set at least 2 settings groups in DIGSI
5 (parameter Number of settings groups > 1). You can set up a maximum of 8 settings groups. The settings
groups set in DIGSI 5 are subsequently loaded into the device.
Mechanism of the Switchover
When switching over from one settings group to another, the device operation is not interrupted. With the
Active settings group
parameter, you are either specifying a certain settings group or you allow
switching
via control
(IEC 60870-5-103, IEC 61850) or
via binary input
.
3.10
3.10.1
3.10.1.1
3.10.1.2
3.10.1.3
System Functions
3.10 Device Settings
162
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...