Parameter:
Directional comparison
,
Release via input signal
•
Default setting
(_:8161:110) Directional comparison
=
no
•
Default setting
(_:8161:112) Release via input signal
=
no
These 2 parameters are not visible in the basic stage.
You use these parameters to define whether the stage is to be used for directional comparison protection.
Directional comparison protection is performed via the
Direction
and
>Release delay & op.
signals.
Parameter Value
Description
no
The stage is not used for directional comparison protection.
yes
If the
Directional comparison
parameter is set to
yes
, the
Release
via input signal
parameter, the
Direction
output signal, and the
>Release delay & op.
input signal become available.
If the
Release via input signal
parameter is set to
yes
, the start of
the time delay, and therefore also the operate signal of the stage, are only
enabled if the
>Release delay & op.
input signal is active. The
>Release delay & op.
input signal must be connected to the release
information from the opposite end (forward information from the
Direc-
tion
output signal); see also the application example in chapter
7.6.10 Application Notes for Directional Comparison Protection
Parameter: Non-directional pickup
•
Recommended setting value
(_:8161:113) Non-directional pickup
=
at volt.< &
mem.empty
This parameter is not visible in the basic stage.
Parameter Value
Description
at volt.< & mem.empty
Select this setting if the stage is to pick up in a non-directional manner if the
voltage memory is empty and determining of direction has to be performed
at low voltages (3-phase close-up fault). An empty voltage memory may
exist, for example, if there is a voltage transformer at the line end and the
CB trips.
Siemens recommends using the default setting.
no
Select this setting if determining of direction is required under all circum-
stances, that is, even in the event of pickup on a 3-phase close-up fault.
Parameter:
Type of character. curve
•
Default setting
(_:8161:130) Type of character. curve
=
IEC normal inverse
The device offers all the usual inverse-time characteristic curves according to IEC and ANSI. Select the
Type
of character. curve
required for your specific application.
Parameter:
Min. time of the curve
•
Default setting
(_:8161:114) Min. time of the curve
=
0.00 s
This parameter is only available in the advanced stage.
With the parameter
Min. time of the curve
, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time. If the
setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommends keeping the default setting of 0 s.
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
684
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...