Average Values
Function Description of Average Values
Average values can be formed based on different measurands:
•
Operational measured values
•
Symmetrical components
Through the settings, you can set how and when the average values are formed. The settings describe:
•
Time slot over which the average value is formed
(Parameter:
Average calc. interval
)
•
Update interval for the display of the average values
(Parameter:
Average update interval
)
•
Synchronization time for establishing the date of commencement updating information, for example, at
the top of the hour (hh:00) or at one of the other times (hh:15, hh:30, hh:45).
(Parameter:
Average synchroniz. time
)
Average values are formed through the following measurands:
•
Operational measured values except for phase-related ratings
•
Amounts of the symmetrical components
You reset the average value formation via the
•
Binary input >Reset average value
•
DIGSI
•
The integrated operation panel
i
i
NOTE
With the
P, Q sign
parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see Chapter
Structure of the
Function, section Inversion of Output-Related Measured and Statistical Values):
•
Active power (total): P total
•
Reactive power (total): Q total
Application and Setting Notes for Average Values
The average value formation functionality is not preconfigured with the devices in the function group. If you
use the functionality, you must load it from the library into the respective function group.
The following settings listed for the calculation of the average values can be set with DIGSI and at the device.
You find the setting parameters in DIGSI in the project tree under Settings > Device settings.
Parameter: Average calc. interval
•
Default setting:
(_:104) Average calc. interval
=
60 min
Parameter Value
Description
1 min to 60 min
Time slot for averaging, for example 60 minutes
Parameter: Average update interval
•
Default setting:
(_:105) Average update interval
=
60 min
9.7
9.7.1
9.7.2
Measured Values, Energy Values, and Supervision of the Primary System
9.7 Average Values
SIPROTEC 5, High-Voltage Bay Controller, Manual
1037
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...