[loMasValue-201507-01.vsd, 1, en_US]
Figure 7-78
Logic Diagram of Measured-Value Selection
Both options are only available for the current-transformer connection types
3-phase + IN
and
3-phase +
IN-separate
. For other connection types respectively, only one option is possible. If you select an option
that is not allowed, an inconsistency message is given.
Depending on the CT secondary rated current, the CT connection type, and the selected setting, the secondary
threshold setting range varies according to the following table.
Table 7-1
Threshold Setting Range
Connec-
tion
Type
Measured
Value
CT
Terminal
Type
Threshold Setting
Range (rated I-sec.:
ph = 1 A, IN = 1 A)
Threshold Setting
Range (rated I-sec.:
ph = 1 A, IN = 5 A)
Threshold Setting
Range (rated I-sec.:
ph = 5 A, IN = 1 A)
Threshold Setting
Range (rated I-sec.:
ph = 5 A, IN = 5 A)
3ph + IN
3I0 calcu-
lated
4 * Protec-
tion
0.010 A to 35.000 A N/A
N/A
0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
N/A
N/A
0.002 A to 8.000 A
IN meas-
ured
4 * Protec-
tion
0.010 A to 35.000 A N/A
N/A
0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
N/A
N/A
0.002 A to 8.000 A
3ph + IN-separate
3I0 calcu-
lated
4 * Protec-
tion
0.010 A to 35.000 A 0.010 A to 35.000 A 0.050 A to 175.00 A 0.050 A to 175.00 A
3 * Protec-
tion, 1 *
sen.
0.010 A to 35.000 A 0.010 A to 35.000 A 0.050 A to 175.00 A 0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
0.001 A to 1.600 A
0.002 A to 8.000 A
0.002 A to 8.000 A
IN meas-
ured
4 * Protec-
tion
0.010 A to 35.000 A 0.050 A to 175.00 A 0.010 A to 35.000 A 0.050 A to 175.00 A
3 * Protec-
tion, 1 *
sen.
0.001 A to 1.600 A
0.002 A to 8.000 A
0.001 A to 1.600 A
0.002 A to 8.000 A
4 * Meas-
urement
0.001 A to 1.600 A
0.002 A to 8.000 A
0.001 A to 1.600 A
0.002 A to 8.000 A
Application and Setting Notes
Parameter:
Measured value
•
Recommended setting value
Measured value
=
IN Measured
This parameter is not available in the basic function.
Parameter Value
Description
7.5.3.2
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
636
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...