Table 3-17
Possible Dropout Values
Signal Type
Dropout Values
SP (single-point indication)
Outgoing, Incoming, Hold
DP (double-point indication)
On, Off, Intermediate Position, Disturbed Position,
Hold
IN (metered values)
0, Hold
MW (measured values)
0, Hold
ACT
Hold
i
i
NOTE
If the protection link fails, these values can be set on the receiver side.
EXAMPLE
2 devices are connected with differential protection via a 64-kbits channel. This is a type 1 topology. 8 bits are
freely available for priority 1. Now, for example, 4 SPS and 2 DPS can be routed:
4 x 1 bit + 2 x 2 bits = 8 bits
i
i
NOTE
Measured values are transmitted as primary values.
Remote Data Transmission: Routing of the Indications and Measured Values to the Protection Interface
The transmission is organized in the form of a data bar which is continuously exchanged between the devices.
For this, see
.
A device indication or measured value is allocated to a definite data area of the bar.
show the routing for a communication topology of protection interface type 1.
To transmit signals to other devices, these signals must be routed in the communication matrix under
Transmit. Binary inputs 1 and 2 are single-point indications (SPS) and are routed to position 1 and position 2
of the transmission with the highest priority (priority 1). For 64 kbit/s, for example, only 8 of these data areas
are available for type 1; they are exchanged between the transmission routes with each telegram. Signals 3
and 4 are double-point indications (DPS), for example, a switch position that is transmitted by a device 1. A
double-point indication occupies 2 positions on the data bar. In addition, a measured and metered value are
communicated via priority 3.
As a measured or metered value uses 32 bits, value 2 starts at position 33. DIGSI 5 indicates the next available
position.
System Functions
3.5 Protection Communication
114
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...