Parameter:
Time dial
•
Default setting
(_:6) Time dial
=
0.2
You can use the
Time dial
parameter to displace the operate curve in the time direction.
General information cannot be provided. Define the value corresponding to the application.
Parameter:
Knee-point
•
Default setting
(_:101) Knee-point current
=
1.300 A
•
Default setting
(_:105) Knee-point time
=
23.60 s
You use the
Knee-point current
parameter and the
Knee-point time
parameter to define the knee-
point of the operate curve.
General information cannot be provided. Define the values corresponding to the application.
Parameter: Minimum Time of the Operate Curve
•
Default setting
(_:104) Min. time of the curve
=
0.80 s
•
Default setting
(_:102) Current at Min. time
=
1.500 A
Via the parameters
Min. time of the curve
and
Current at Min. time
, the point of the operate
curve is defined where higher currents do no longer cause shorter operate times.
General information cannot be provided. Define the value corresponding to the application.
Parameter: Maximum Time of the Operate Curve
•
Default setting
(_:103) Max. time of the curve
=
93.00 s
You can use the parameter
Max. time of the curve
to determine the initial value of the operate curve
(for 3I0 =
Threshold
).
General information cannot be provided. Define the value corresponding to the application.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:1
Log.inv.T KP #:Mode
•
off
•
on
•
test
off
_:2
Log.inv.T KP #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:108
Log.inv.T KP #:Direc-
tional mode
•
forward
•
reverse
forward
_:8
Log.inv.T KP #:Method
of measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:107
Log.inv.T KP #:Direc-
tional comparison
•
no
•
yes
no
_:106
Log.inv.T KP #:Release
via input signal
•
no
•
yes
no
_:10
Log.inv.T KP #:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:27
Log.inv.T KP #:Blk. w.
inrush curr. detect.
•
no
•
yes
no
7.7.8.3
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
738
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...