with I< & aux.contact
With the criteria
with I<
and
with I< & aux.contact
, the condition of the circuit breaker is also
taken into account as a further criterion in addition to the dropout of the tripping function (operate indi-
cation is terminated by command). You can select whether the state is determined by means of the
current (
with I<
) or by means of the current in conjunction with the circuit-breaker auxiliary contacts
(
with I< & aux.contact
). The behavior of these setting options only differs in one situation of the
circuit-breaker condition. If the circuit breaker is in the opening condition, the trip command is reset in
the case of the option
with I<
, whereas it is not reset yet in the case of the option with
with I< &
aux.contact
. The opening condition is detected when the auxiliary contacts still detect the circuit
breaker as being closed and opening is detected via the decreasing current flow.
As long as the circuit breaker is detected unambiguously as closed (fully closed), the trip command will
not be reset with these setting options.
The information about the condition of the circuit breaker is supplied by the Circuit-breaker position
recognition function block (see
). The determination of the various conditions is also
described in this chapter.
Application and Setting Notes
Parameter: 1-pole tripping permitted
For this, see
5.6.3 Application and Setting Notes
Parameter: 3-Pole Coupling
•
Default setting
(_:5341:102) 3-pole coupling
=
with trip
Parameter Value
Description
with trip
With this setting, every multipole trip command results in 3-pole tripping. If a 1-
phase short circuit is present within the tripping zone and any other fault is
present outside the zone, 1-pole tripping is possible.
Even an additional fault during 1-pole tripping also results in 3-pole coupling
only if it occurs within the tripping zone.
with pickup
With this setting every multiphase pickup results in a 3-pole trip, even if only
one 1-phase ground fault is present in the tripping zone and one further fault is
detected, for example due to overcurrent.
Even if a 1-pole trip command is pending, any further pickup will result in a 3-
pole coupling.
EXAMPLE
If 2 1-phase ground faults occur on different lines - for example, including parallel lines - (see
protection devices will detect fault types A-B-E at all 4 line ends, that is, with a pickup characteristic corre-
sponding to a 2-phase ground fault. However, since there is only one 1-phase short circuit on each of the 2
lines, it is desirable to have a short 1-pole interruption on each of these 2 lines. This is possible with a setting
with trip command. Each of the 4 devices detects an internal 1-phase short circuit and can therefore cause 1-
pole tripping.
[dwfehler-030211-01.tif, 1, en_US]
Figure 5-36
Multiphase Short Circuit on a Double Line
5.6.4.2
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
234
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...