[dw_GPP PQ diagram, 2, en_US]
Figure 7-175
Pickup Values and Characteristic Curves
Setting Notes for the Active Power Stage
Stage Type
In the following example, a drop of the active power below a threshold is to be monitored. In the 3-phase
circuit breaker (P, Q) function, work with the stage type Power P<.
Parameter: Measured value
•
Recommended setting value
(_:6271:105) Measured value
=
positive seq. power
The
Measured value
parameter is used to specify which measured power value is evaluated. For 3-phase
measurement, Siemens recommends to evaluate the positive-sequence system power.
Parameter: Threshold
•
Recommended setting value
(_:6271:3) Threshold
=
0 %
The
Threshold
parameter is used to define the pickup threshold of the active power stage. In the example,
the pickup characteristic runs across the point of origin of the coordinates. Set the parameter
Threshold
to
0 %
.
i
i
NOTE
If you use several settings groups, consider the following:
•
The dropout value of a stage must have the same sign in all settings groups.
•
Switching from a positive dropout value to a negative dropout value or vice versa is not allowed. As a
result, DIGSI reports an inconsistency.
•
If you want to change the sign of the dropout value of a stage in an additional settings group, instan-
tiate a new stage and enable it. If the new stage should not be effective in another settings group,
disable the stage there.
Parameter: Dropout ratio
•
Recommended setting value
(_:6271:101) Dropout ratio
=
1.05
A hysteresis of 5 % is sufficient for most applications. The setting value for the lower stage is therefore 1.05.
7.22.6
Protection and Automation Functions
7.22 Power Protection (P,Q), 3-Phase
SIPROTEC 5, High-Voltage Bay Controller, Manual
857
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...