Description
Logic of the Stage
[lo3phinv, 2, en_US]
Figure 7-142
Logic Diagram of the Inverse-Time Overvoltage Protection with 3-Phase Voltage
Method of Measurement
Use the
Method of measurement
parameter to define whether the stage uses the
fundamental comp.
or the
RMS value
.
•
Measurement
fundamental comp.
:
This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.
•
Measurement
RMS value
:
This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.
7.13.7
Protection and Automation Functions
7.13 Overvoltage Protection with 3-Phase Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual
789
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...