You can set the voltage controller operating mode using the
Operating mode
parameter or the Operating
mode command to automatic operation or manual operation. In automatic operation, the voltage is
controlled automatically in accordance with the set parameters.
Three-Winding Transformer Voltage Controller
For the two-winding transformer voltage controller, the measurands that are used to manage the feedback
control are permanently defined.
With the voltage controller for the three-winding transformer, these measurands can be specified using one
parameter (parameter
Winding selection
=
Winding 1
or
Winding 2
) or they can be automatically
selected (
Winding selection
=
WithMaxLoad
).
The winding is automatically selected by evaluating the load current in the windings. If the load current in one
of the two windings is greater than the load current in the other winding by 5 % of the rated current for 10 s,
then the winding voltage is controlled using the larger load current.
Grid Coupling Transformer Voltage Controller
For the two-winding transformer voltage controller, the measurands that are used to manage the feedback
control are permanently defined.
With the grid coupling transformer voltage controller, these measurands can be selected using a parameter
(parameter
Winding selection
=
Winding 1
or
Winding 2
).
You can change the winding selection during operation using the settings group switching.
You can monitor the power-flow direction. If the difference in the power of
Winding 1
and
Winding 2
is
greater than 10 % of the rated power on the control side, the indication
Power-flow superv.
appears and
the function switches to alarm status.
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
457
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...