Addr.
Parameter
C
Setting Options
Default Setting
_:6601:102
General:CB ready check
bef. start
•
no
•
yes
no
_:6601:103
General:Reclai. time
aft.succ.cyc.
0.50 s to 300.00 s
3.00 s
_:6601:104
General:Block. time aft.
man.close
0.00 s to 300.00 s
1.00 s
_:6601:105
General:Start signal
supervis.time
0.01 s to 300.00 s
0.13 s
_:6601:106
General:CB ready superv.
time
0.01 s to 300.00 s
3.00 s
_:6601:107
General:3-pole operate
by 79
•
no
•
yes
yes
_:6601:108
General:Evolving-fault
detection
•
with trip
•
with pickup
with trip
_:6601:109
General:Response to
evolv. faults
•
strt. evol.flt.dead time
•
blocks 79
blocks 79
_:6601:110
General:Max. dead-time
delay
0.01 s to 300.00 s
0.50 s
_:6601:111
General:Max. dead-time
extension
0.00 s to 300.00 s; ∞
1.20 s
_:6601:112
General:Send delay f.
remot. close
0.00 s to 300.00 s; ∞
∞
DLC, RDT
_:6601:113
General:Dead-line check/
reduc.d.t
•
without
•
Reduced dead t. RDT
•
Dead-line check DLC
without
_:6601:114
General:Voltage supervi-
sion time
0.10 s to 30.00 s
0.10 s
_:6601:115
General:Volt. thres.f. live
line/bus
0.300 V to 340.000 V
48.000 V
_:6601:116
General:Volt.thres. f.
dead line/bus
0.300 V to 340.000 V
30.000 V
Cycle 1
_:6571:102
Cycle 1:Start from idle
state allow.
•
no
•
yes
yes
_:6571:103
Cycle 1:Action time
0.00 s to 300.00 s; ∞
0.20 s
_:6571:108
Cycle 1:Dead time aft. 3-
pole trip
0.00 s to 1800.00 s; ∞
0.50 s
_:6571:107
Cycle 1:Dead time aft. 1-
pole trip
0.00 s to 1800.00 s; ∞
1.20 s
_:6571:104
Cycle 1:Dead time aft.
1ph. pickup
0.00 s to 1800.00 s; ∞
1.20 s
_:6571:105
Cycle 1:Dead time aft.
2ph. pickup
0.00 s to 1800.00 s; ∞
1.20 s
_:6571:106
Cycle 1:Dead time aft.
3ph. pickup
0.00 s to 1800.00 s; ∞
0.50 s
_:6571:109
Cycle 1:Dead time aft.
evolv. fault
0.01 s to 1800.00 s
1.20 s
_:6571:111
Cycle 1:CB ready check
bef.close
•
no
•
yes
no
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
577
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...