Analog Channel Supervision via Fast Current Sum
Times
Pickup times
Approx. 2 ms (faster than the fastest protection function)
Dropout time
Approx. 100 ms
Blockings
Blocked functions
All functions that process the measured values from this current meas-
uring point (for example, differential protection).
11.44
Technical Data
11.44 Analog Channel Supervision via Fast Current Sum
1192
SIPROTEC 5, High-Voltage Bay Controller, Manual