Parameter Value
Description
yes
When the transformer inrush-current detection detects an inrush current that
would lead to an operate of the stage, the start of the operate delay and
operate of the stage are blocked.
Select this setting if the device is used on transformers and the threshold
value of the stage is set below the maximum inrush current of the trans-
former. This applies to the overcurrent-protection stage, which is used as a
backup stage with grading time for faults on the undervoltage side of the
transformer.
Parameter:
Threshold
•
Default setting
(_:4861:3) Threshold
=
1.20 A
For setting the threshold value, the same considerations apply as for the non-directional overcurrent protec-
tion function.
For further information, refer to chapter
7.5.4.2 Application and Setting Notes
Parameter:
Dropout ratio
•
Recommended setting value
(_:4861:4) Dropout ratio
=
0.95
This parameter is not visible for the basic stage.
The recommended setting value of
0.95
is appropriate for most applications.
For high-precision measurements, the setting value of the
Dropout ratio
parameter can be reduced, for
example to 0.98. If you expect highly fluctuating measurands at the pickup threshold, you can increase the
setting value of the
Dropout ratio
parameter. This avoids chattering of the stage.
Parameter: Dropout delay
•
Recommended setting value
(_:4861:101) Dropout delay
=
0 s
This parameter is not visible for the basic stage.
Siemens recommends using the dropout delay of 0 s, since the dropout of a protection stage must be
performed as fast as possible.
You can use the
Dropout delay
parameter ≠
0 s
to obtain a uniform dropout behavior if you use it
together with an electromechanical relay. This is required for time grading. The dropout time of the electro-
mechanical relay must be known for this purpose. Subtract the dropout time of your own device (see Tech-
nical data) and set the result.
Parameter:
Operate delay
•
Default setting
(_:4861:6) Operate delay
=
0.300 s
(for the 1st stage)
The
Operate delay
to be set is derived from the time-grading chart that has been prepared for the system.
Typical examples of grading times are provided in sections
7.6.9 Application Notes for Parallel Lines
7.6.10 Application Notes for Directional Comparison Protection
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:4861:1
Definite-T 1:Mode
•
off
•
on
•
test
off
_:4861:2
Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:4861:105
Definite-T 1:Directional
mode
•
forward
•
reverse
forward
7.7.5.3
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
715
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...