Supervision of Communication Connections
SIPROTEC 5 devices offer extensive communication possibilities via fixed and optional interfaces. Beyond the
hardware supervision of the communication plug-in modules the transferred data must be monitored with
respect to their consistency, failure, or outage.
Supervision
With the supervision of the communication connections, every communication port is monitored selectively.
•
Failures are detected and indicated via the operational log. The device remains in operation!
•
Each port additionally is equipped with a separate communication log, with which details of the failures
(for example, error rate) are displayed.
Marking Fault Signals/Data
The signals/data affected by the failure are marked as invalid. In this way, the affected protection functions
can go into a secure state. In the following, some examples are named:
•
GOOSE signals can automatically be set to defined values in case of disturbed IEC 61850 communication.
•
Disturbed protection interfaces set phasor values, both analog measured values and binary information
to invalid (for example, for differential protection). Binary signal traces can be set to defined values in
cases of failures.
•
Disturbed time-synchronization signals can lead to an automatic change of the source of time synchroni-
zation.
Normally, you can correct communication failures by checking the external connections or by replacing the
affected communication modules. In chapter to
, you will find the detailed description,
in tabular form, of the error responses. Corresponding corrective measures can also be found there.
8.7
Supervision Functions
8.7 Supervision of Communication Connections
982
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...