[DwMinTime_20140708-01.vsd, 1, en_US]
Figure 7-114
Minimum Operating Time of the Curve
Additional Time Delay (Advanced Stage)
With the parameter
Additional time delay
, you define a definite-time delay in addition to the inverse-
time delay. With this setting, the whole curve is shifted on the time axis by this additional definite time.
Blocking of the Stage (Basic and Advanced Stage)
The following blockings reset the picked up stage completely:
•
Externally or internally via the binary input signal
>Block stage
)
•
Measuring-voltage failure (see chapter
•
Via the dynamic settings functionality (only available in the advanced function type, see Influence of
Other Functions via Dynamic Settings and chapter
7.7.10 Influence of Other Functions via Dynamic
)
Blocking of the Operate Delay (Basic and Advanced Stage)
You can use the binary input signal
>Block delay & op.
to prevent the start of the operate delay and thus
also the generation of the operate signal. A running operate delay is reset. The pickup is indicated. Fault
logging and fault recording take place.
Blocking of the Operate Delay and Operate Signal via the Device-Internal Inrush-Current Detection Function (Basic
and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter Blocking of the Tripping by Device-Internal Inrush-Current Detection
For more information, refer to
.
Directional Comparison Protection (Advanced Stage)
The stage can be used for directional comparison protection. This is set using the
Directional compar-
ison
parameter. With the
yes
setting, the direction indication
Direction
is released and the direction
(forward or reverse) is determined, if the current exceeds the threshold of the stage. The direction indicated is
independent of the directional mode set for the stage.
The
Release via input signal
parameter and the
>Release delay & op.
input signal are available
with directional comparison protection. If the
Release via input signal
parameter is set to
yes
, the
start of the operate delay, and therefore the operate signal of the stage, are only enabled when the
>Release delay & op.
input signal is active.
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
722
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...