Addr.
Parameter
C
Setting Options
Default Setting
_:19
User curve #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:107
User curve #:Time dial
0.05 to 15.00
1.00
Information List
No.
Information
Data Class
(Type)
Type
User curve #
_:81
User curve #:>Block stage
SPS
I
_:501
User curve #:>Release delay & op.
SPS
I
_:84
User curve #:>Activ. dyn. settings
SPS
I
_:500
User curve #:>Block delay & op.
SPS
I
_:54
User curve #:Inactive
SPS
O
_:52
User curve #:Behavior
ENS
O
_:53
User curve #:Health
ENS
O
_:60
User curve #:Inrush blocks operate
SPS
O
_:62
User curve #:Dyn.set. AR cycle1act.
SPS
O
_:63
User curve #:Dyn.set. AR cycle2act.
SPS
O
_:64
User curve #:Dyn.set. AR cycle3act.
SPS
O
_:65
User curve #:Dyn.set. ARcycl.>3act
SPS
O
_:66
User curve #:Dyn.set. CLP active
SPS
O
_:67
User curve #:Dyn.set. BI active
SPS
O
_:68
User curve #:Dyn. set. blks. pickup
SPS
O
_:59
User curve #:Disk emulation running
SPS
O
_:55
User curve #:Pickup
ACD
O
_:300
User curve #:Direction
ACD
O
_:56
User curve #:Operate delay expired
ACT
O
_:57
User curve #:Operate
ACT
O
Influence of Other Functions via Dynamic Settings
7.5.8.2 Application and Setting Notes (Advanced Stage)
describe the influence of
other functions on dynamic settings.
7.7.9.4
7.7.10
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
745
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...