Parameter Value
Description
no
The transformer inrush-current detection does not affect the stage.
Select this setting in the following cases:
•
In cases where the device is not used on transformers.
•
In cases where the device is used on transformers and the threshold
value of the stage is set above the maximum inrush current of the
transformer. This, for example, applies to the high-current stage that is
set such according to the short-circuit voltage V
sc
of the transformer
that it only picks up on faults from the high-voltage side. The trans-
former inrush current cannot become larger than the maximum trans-
mittable short-circuit current.
yes
When the transformer inrush-current detection detects an inrush current
that would lead to a tripping of the stage, the start of the time delay and
tripping of the stage are blocked.
Select this setting if the device is used on transformers and the threshold
value of the stage is set below the maximum inrush current of the trans-
former. This applies to the overcurrent-protection stage, which is used as a
backup stage with grading time for faults on the undervoltage side of the
transformer.
Influence of Other Functions via Dynamic Settings
Description
The
Threshold
and
Operate delay
settings used for tripping are so-called
dynamic settings
.
Depending on other functions, the settings of these parameters can be changed dynamically. Depending on
other functions, the stage can also be blocked dynamically. This functionality is only available in function type
Advanced.
7.5.8
7.5.8.1
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
662
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...