Addr.
Parameter
C
Setting Options
Default Setting
_:103
Mes.v.fail.det:3ph.fail. -
phs.curr. jump
1 A @ 100 Irated 0.030 A to 35.000 A
0.100 A
5 A @ 100 Irated 0.15 A to 175.00 A
0.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
0.100 A
5 A @ 50 Irated
0.15 A to 175.00 A
0.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.100 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.500 A
_:101
Mes.v.fail.det:3ph.fail. -
VA,VB,VC <
0.300 V to 340.000 V
5.000 V
_:107
Mes.v.fail.det:Switch-on
3ph. failure
•
off
•
on
on
_:106
Mes.v.fail.det:SO
3ph.fail. - time delay
0.01 s to 30.00 s
3.00 s
Information List
No.
Information
Data Class
(Type)
Type
Mes.v.fail.det
_:82
Mes.v.fail.det:>Block function
SPS
I
_:54
Mes.v.fail.det:Inactive
SPS
O
_:52
Mes.v.fail.det:Behavior
ENS
O
_:53
Mes.v.fail.det:Health
ENS
O
_:300
Mes.v.fail.det:Alarm
SPS
O
_:304
Mes.v.fail.det:Asym.fail.-inst.alarm
SPS
O
_:303
Mes.v.fail.det:Asym.fail.-alarm
SPS
O
_:301
Mes.v.fail.det:3ph.failure-alarm
SPS
O
_:302
Mes.v.fail.det:SO 3ph.failure-alarm
SPS
O
Signaling-Voltage Supervision
Overview of Functions
Signaling-voltage supervision is used to evaluate the validity of binary signals connected to the SIPROTEC
device via binary inputs. For this purpose, one binary input is used to monitor the signaling voltage. If the
signaling voltage fails, the associated binary signals are marked as invalid and a Signaling-voltage malfunc-
tion indication is issued.
Several signaling-voltage supervision groups can be created in one SIPROTEC device. Each of these groups
monitors an adjustable area with binary inputs.
Structure of the Function
The Signaling-voltage supervision function group contains, besides the general functionality, one preinstan-
tiated Supervision group stage. The Supervision group stage can be instantiated in DIGSI 5 multiple times.
8.3.2.8
8.3.3
8.3.3.1
8.3.3.2
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, High-Voltage Bay Controller, Manual
945
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...