Automatic Reclosing Function
Overview of Functions
The Automatic reclosing function:
•
Automatically closes overhead lines after arc short-circuits
•
Is only permissible for overhead lines, because only the possibility of self-activated extinguishing of an
arc short-circuit exists here
•
Can be controlled by integrated protection functions and by external protection devices
•
The automatic reclosing can occur through an external automatic reclosing function via binary inputs.
The automatic reclosing after switching off through a short-circuit protection is taken over by the automatic
reclosing function (AREC). The following figure shows an example for the normal procedure with a two-time
automatic reclosing where the second automatic reclosing attempt is successful.
[dw2awewz-090210-01.tif, 1, en_US]
Figure 7-19
Process Diagram of a Two-Time Reclosing With Action Time (2nd Reclosing Successful)
The integrated Automatic reclosing function allows for up to 8 reclosing attempts. Each of the 8 disruption
cycles can work with different parameters.
Structure of the Function
The automatic reclosing function is used in function groups for circuit breakers. In a function group for circuit
breakers, one of the 3 types of functions illustrated in the following figures can be used. The Automatic
reclosing function has a central function control.
[dwfktawe-100611-01.tif, 1, en_US]
Figure 7-20
Structure/Embedding of the Function
Cyclic Automatic Reclosing Function
The Cyclic automatic reclosing function (
) allows for up to 8 reclosing attempts. Here each disrup-
tion cycle may work with different settings.
7.2
7.2.1
7.2.2
Protection and Automation Functions
7.2 Automatic Reclosing Function
542
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...