Addr.
Parameter
C
Setting Options
Default Setting
_:3
Log.inv.T KP #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:109
Log.inv.T KP #:Time dial
0.05 to 1.50
0.20
_:101
Log.inv.T KP #:Knee-
point current
1 A @ 100 Irated 0.030 A to 35.000 A
1.300 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.300 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.300 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.500 A
_:105
Log.inv.T KP #:Knee-
point time
0.00 s to 100.00 s
23.60 s
_:102
Log.inv.T KP #:Current at
Min. time
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:104
Log.inv.T KP #:Min. time
of the curve
0.00 s to 30.00 s
0.80 s
_:103
Log.inv.T KP #:Max. time
of the curve
0.00 s to 200.00 s
93.00 s
Information List
No.
Information
Data Class
(Type)
Type
Stage #
_:81
Log.inv.T KP #:>Block stage
SPS
I
_:501
Log.inv.T KP #:>Release delay & op.
SPS
I
_:500
Log.inv.T KP #:>Block delay & op.
SPS
I
_:54
Log.inv.T KP #:Inactive
SPS
O
_:52
Log.inv.T KP #:Behavior
ENS
O
_:53
Log.inv.T KP #:Health
ENS
O
_:60
Log.inv.T KP #:Inrush blocks operate
SPS
O
_:55
Log.inv.T KP #:Pickup
ACD
O
_:300
Log.inv.T KP #:Direction
ACD
O
_:56
Log.inv.T KP #:Operate delay expired
ACT
O
_:57
Log.inv.T KP #:Operate
ACT
O
7.7.8.4
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
739
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...