Reading on the Device via the On-Site Operation Panel
•
To reach the operational log via the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → Operational log
•
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
•
Using the Info softkey, you can retrieve auxiliary information on the entry depending on the context.
[scoperlog1-081217-01, 1, en_US]
Figure 3-5
On-Site Display of an Indication List (Example: Operational Indications)
Deletability
The operational log of your SIPROTEC 5 device can be deleted. This is done usually after testing or commis-
sioning the device. To know more about this, read chapter
3.1.6 Saving and Deleting the Logs
.
Configurability
The indication scope of the operational log is configured in a specifically defined column of the information
routing (matrix) of DIGSI 5:
Target → Log → Operational log column
Selected application templates and functions from the library bring with them a predefined set of operational
indications which you can adjust individually at any time.
Fault Log
Fault indications are events which arise during a fault. They are logged in the fault log with real-time stamp
and relative-time stamp (reference point: fault occurrence) . Faults are numbered consecutively in rising order.
With fault recording engaged, a corresponding fault record with the same number exists for every fault logged
in the fault log. A maximum of 128 fault logs can be stored. A maximum of 1000 indications can be recorded
in each fault log.
Fault Definition
In general, a fault is started by the raising pickup of a protection function and ends with the cleared pickup
after the trip command.
When using an automatic reclosing function, the complete reclosing cycle (successful or unsuccessful) is pref-
erably integrated into the fault. If evolving faults appear within reclosing cycles, the entire clearing process is
logged under one fault number even in multiple pickup cycles. Without automatic reclosing function every
pickup is also recorded as its own fault.
User-defined configuration of a fault is also possible.
3.1.5.3
System Functions
3.1 Indications
56
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...