Measurement of the fundamental comp.:
This method of measurement processes the sampled current values and filters out the fundamental
component numerically.
•
Measurement of the RMS value:
This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.
Voltage-Dependent Pickup Threshold
The pickup threshold of the overcurrent stage depends on the voltage magnitude. A lower voltage decreases
the current pickup value (see
). In the range between V/V
rated
= 1.00 to 0.25 a linear, directly
proportional dependence is realized.
[dwvolpic-220713-01.tif, 1, en_US]
Figure 7-138
Voltage Influence of the Pickup Threshold
With:
V
=
Measured phase-to-phase voltage
V
rated
=
Rated voltage (parameter Rated voltage in the function block General of the protec-
tion function group)
PU sett.
=
Pickup threshold setting (parameter address: _11491:3)
PU(V)
=
Applied pickup threshold according to the voltage influence
The minimum current pickup threshold value is 0.03 * Irated. This value cannot be decreased any further even
not by voltage-dependent pickup threshold factor.
Decreasing the pickup threshold is carried out phase-selectively. The assignment of voltages to current-
carrying phases is shown in
.
Table 7-8
Controlling Voltages in Relation to the Fault Current
Current
Controlling Voltage
I
A
V
AB
I
B
V
BC
I
C
V
CA
Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI
When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed.
Protection and Automation Functions
7.12 Voltage-Dependent Overcurrent Protection
776
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...