Application and Setting Notes
Parameter: Maximum Differential Values of Voltage, Frequency and Angle
•
Default setting
(_:5071:122) Max. voltage diff. V2>V1
=
5.0 V
•
Default setting
(_:5071:123) Max. voltage diff. V2<V1
=
5.0 V
•
Default setting
(_:5071:117) Max. frequency diff. f2>f1
=
0.10 Hz
•
Default setting
(_:5071:118) Max. frequency diff. f2<f1
=
0.10 Hz
•
Default setting
(_:5071:124) Max. angle diff. α2>α1
=
10
o
•
Default setting
(_:5071:125) Max. angle diff. α2<α1
=
10
o
2 parameters are available for the differential values voltage, frequency, and angle. Unbalanced closing ranges
can be set with this, if required.
The permissible differential values must ensure that no protection tripping or damage occurs in the system
owing to compensation processes (circulating current) and power swings after interconnection of the parts of
the power system. The settings must not be configured too closely on the other side so that necessary
closures are not blocked.
Typical differential values are selected in the default setting. Depending on the system, the settings must be
checked and adjusted, if necessary.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:5071:1
Synchrocheck 1:Mode
•
off
•
on
•
test
off
_:5071:101
Synchrocheck 1:Min.
operating limit Vmin
0.300 V to 340.000 V
90.000 V
_:5071:102
Synchrocheck 1:Max.
operat. limit Vmax
0.300 V to 340.000 V
110.000 V
_:5071:110
Synchrocheck
1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞
30.00 s
_:5071:108
Synchrocheck 1:Direct
close command
•
no
•
yes
no
_:5071:126
Synchrocheck 1:Voltage
adjustment
0.500 to 2.000
1.000
De-en.gized switch.
_:5071:105
Synchrocheck 1:Close
cmd. at V1< & V2>
•
no
•
yes
no
_:5071:106
Synchrocheck 1:Close
cmd. at V1> & V2<
•
no
•
yes
no
_:5071:107
Synchrocheck 1:Close
cmd. at V1< & V2<
•
no
•
yes
no
_:5071:103
Synchrocheck 1:V1, V2
without voltage
0.300 V to 170.000 V
5.000 V
_:5071:104
Synchrocheck 1:V1, V2
with voltage
0.300 V to 340.000 V
80.000 V
_:5071:109
Synchrocheck 1:Supervi-
sion time
0.00 s to 60.00 s
0.10 s
6.4.7.2
6.4.7.3
Control Functions
6.4 Synchronization Function
378
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...