Parameter:
Moving contact (highest binary input)
•
Default setting
Moving contact (highest binary input)
=
no
If the tap position is not to be recognized as valid and accepted until the motor sliding contact signals that it
has reached the taps, then activate the
Moving contact (highest binary input)
option. If this
parameter is set, the new position is only labeled with an * when the moving contact drops out.
Parameter:
Software filter time
•
Default setting
Software filter time
=
1000 ms
With this parameter, you specify the
Software filter time
for capturing the tap position. The range of
values extends from 0 ms to 86400000 ms. Within this time, brief changes on the binary inputs are
suppressed.
Parameter:
Retrigger filter
•
Default setting
Retrigger filter
=
Yes
With this parameter, you switch retriggering of the filtering time by a position change on or off.
Parameter:
Indication timestamp before filtering
•
Default setting
Indication timestamp before filtering
=
no
With this parameter, you specify whether the hardware filtering time is accounted for in the time stamp of
position capture.
Parameter:
Chatter blocking
•
Default setting
Chatter blocking
=
no
With this parameter, you switch
Chatter blocking
on or off.
Settings (Properties Dialog)
The settings listed here can only be reached and changed by way of the Properties dialog of the Position
Controllable.
Addr.
Parameter
C
Range of Values
Default Setting
General Information
-
Minimum value
Calculated
-
-
Maximum value
Calculated
-
-
Tap-display offset
–63 to +63
0
-
Number of bits f. tap code
2 to 32
4
-
Number of tap positions
2 to 63
15
-
Tap-coding type
•
binary
•
1-of-n
•
BCD
•
table
•
BCD signed
•
gray
binary
Software filter
-
Software filter time
0 ms to 86400000 ms
500 ms
6.8.3
Control Functions
6.8 Transformer Tap Changers
SIPROTEC 5, High-Voltage Bay Controller, Manual
447
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...