Dropout Delay (Advanced Stage)
If the value falls below the dropout threshold, the dropout can be delayed. The pickup is maintained for the
specified time. The tripping delay continues to run. If the time delay expires while the pickup is still main-
tained, the stage operates.
Blocking of the Stage (Basic and Advanced Stage)
The following blockings reset the picked up stage completely:
•
Via the binary input signal
>Block stage
from an external or internal source
•
Via the functionality of the
dynamic settings
(see chapter Influence of other functions via
dynamic settings and section
).
Blocking of the Time Delay (Basic and Advanced Stage)
You can use the binary input signal
>Block delay & op.
to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.
Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter
Influence of Other Functions via Dynamic Settings (Advanced Stage)
If available in the device, the following functions can influence the overcurrent-protection stages:
•
Automatic reclosing
•
Cold-load pickup detection
•
Binary input signal
The influence of these functions via dynamic settings is described in chapter
.
Application and Setting Notes
Parameter:
Method of measurement
•
Recommended setting value
(_:751:8) Method of measurement
=
fundamental comp.
With the
Method of measurement
parameter, you define whether the stage uses the
fundamental
comp.
(standard method) or the calculated
RMS value
.
Parameter Value
Description
fundamental comp.
Select this method of measurement if harmonics or transient current peaks
are to be suppressed.
Siemens recommends using this method as the standard method.
RMS value
Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Consider that aperiodic DC
components present in the secondary circuit are measured and can cause
an overfunction.
For this method of measurement, do not set the
threshold value
of the
stage to less than 0.1 I
rated,sec
. If currents from more than one measuring
point are added up in the current interface of a function group, the setting
value should not be set lower than 0.1 I
rated,sec
multiplied by the number of
added currents.
7.5.4.2
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
640
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...