Function Blocks
UM353-1B
April
2012
3-28
3.2.19 BATSW - Batch Switch
BATSW
function blocks can be used on a one per loop
basis. Each is used with a PID function block to eliminate
overshoot during startup conditions. When placed in the
feedback path of the controller it causes the reset
component of the controller to be reduced (if controller
action is Rev). Without the use of a batch switch during
startup, the controller output (O1 = GE + R) will equal
full output since the reset will wind up. This requires the
process to overshoot the setpoint in order to bring the
controller output back down. With a batch switch in the
feedback path, a lower reset value will be present when
crossover occurs, thus reducing or eliminating overshoot.
As input A equals or exceeds the HI or LO LIMIT setting,
the output of the batch switch will be either decreased (HI
LIMIT) or increased (LO LIMIT), changing the feedback signal and therefore the controller reset signal. This
maintains controller output at the batch switch limit setting and eliminates reset windup.
If a controller has a large proportional gain setting, the reset can be modified too much, such that the process may
under shoot the setpoint during a startup condition. The BPL (Batch Pre-Load) is adjusted to optimize the controller
for startup conditions by limiting how much the batch switch can adjust the controller feedback signal.
When the controller output is within its normal operating output, the batch switch has no effect on the controller.
This allows the controller to be tuned optimally for normal operating conditions and the batch switch to add
additional compensation, very similar to derivative action, only during startup.
BLOCK DIAGRAM
A
O
utput
-
GAIN
HI
Selector
LO
Selector
+
+
+
GAIN
LO
Selector
HI
Selector
+
+
+
B
atch
P
re-
L
oad
HI LIMIT
LO LIMIT
-
O1
.
.
Rev 2
Input
A
BATCH SWITCH
T
I
H I
O
L
I N
U
A
I
A
G
N
HI
gh
LIMIT
(S)
........................... Real (100.0)
LO
w
LIMIT
(S)
........................... Real (0.0)
INPUT A
(H)
....
loop tag.block tag.output (null)
GAIN
(S)
.................................... Real (32.0)
O1
O
utput
1
BATCH SWITCH
BATSW
ESN = 000
I
M
L
T
P
A
L I M I T
E S N
E
xec.
S
eq.
N
o.
(H)
........... 001 to 250
P
B
L
B
atch
P
re-
L
oad
(S)
.................. Real (50.0)
Содержание 353
Страница 12: ...Contents UM353 1B x April 2012 ...
Страница 22: ...Introduction UM353 1B April 2012 1 10 ...
Страница 30: ...Configuration Overview UM353 1B April 2012 2 8 ...
Страница 122: ...Function Blocks UM353 1B April 2012 3 92 ...
Страница 168: ...Data Mapping UM353 1B April 2012 6 28 ...
Страница 204: ...Controller and System Test UM353 1B April 2012 9 8 ...
Страница 222: ...Calibration UM353 1B April 2012 11 4 ...
Страница 226: ...Circuit Description UM353 1B April 2012 12 4 ...
Страница 238: ...Model Designation and Specifications UM353 1B April 2012 13 12 EC Declaration of Conformity ...
Страница 239: ...UM353 1B Model Designation and Specifications April 2012 13 13 Annex A to the EC Declaration of Conformity ...
Страница 240: ...Model Designation and Specifications UM353 1B April 2012 13 14 ...
Страница 244: ...Abbreviations And Acronyms UM353 1B 14 4 April 2012 ...