Factory Configured Options
UM353-1B
April
2012
4-10
4.6 FCO106 - Single Loop Controller w/ Operator Setpoint Limits
Factory Configured Option FCO106 provides a single loop controller configured in Loop01. This is similar to
FCO101 but with a SPLIM block added to the output of the SETPT block. A block diagram of the loop
configuration is shown below along with any
changes
to the default parameter values of the configured blocks.
This configuration provides setpoint tracking. If a fixed setpoint is desired, the TC input to the SETPT function
block can be set to UNCONFIG. If the loop tag ‘LOOP01’ is changed, all configured references will automatically
be changed to the new tag.
SETPT
TV
TC
O1
AIN1
QS
O1
AOUT1
QS
ALARM
A1
A2
A3
A4
A/M
O1
AS
NA
MS
ES
SS
SPLIM
HS
O1
LS
PID
O1
AE
AW
SR
P
D
A
TV
TC
EM
S
D
P
S
F
A
I
A
LU
LD
Valve
Process
S
P
V
.
.
LOOP01
A/M - Auto/Manual Function Block
RG PTR - Range Pointer ------------ Loop01.PID.OR
INPUT A - Input A ------------------- Loop01.PID.O1
ESN - Exec. Seq. No. --------------- 25
AOUT1 - Analog Output 1 Function Block
RG PTR - Range Pointer ------------ Loop01.PID.OR
INPUT S - Input S ------------------- Loop01.A/M.O1
ODC - Operator Display for Controllers
P RG PTR - P Range Pointer ------- Loop01.AIN1.OR
V RG PTR - V Range Pointer ------ Loop01.PID.OR
INPUT P - Input P (Process) ------- Loop01.AIN1.O1
INPUT S - Input S (Setpoint) ------ Loop01.SPLIM.O1
INPUT V - Input V (Valve) -------- Loop01.A/M.O1
LOOP # - Loop # ------- 01
SETPT - Setpoint Function Block
RG PTR - Range Pointer ----------- Loop01.AIN1.OR
INPUT TV - Input TV -------------- Loop01.AIN1.O1
INPUT TC - Input TC -------------- Loop01.A/M.NA
INPUT LU - Input LU -------------- Loop01.SPLIM.HS
INPUT LD - Input LD -------------- Loop01.SPLIM.LS
ESN - Exec. Seq. No.--------------- 5
SPLIM - Setpoint Limit Function Block
RG PTR - Range Pointer ---------- Loop01.AIN1.OR
INPUT A - Input A ---------------- Loop01.SETPT.O1
ESN - Exec. Seq. No. ------------- 10
ALARM - Alarm Function Block
RG PTR - Range Pointer ---------- Loop01.AIN1.OR
INPUT P - Input P ----------------- Loop01.AIN1.O1
INPUT D - Input D ---------------- Loop01.SPLIM.O1
ESN - Exec. Seq. No. ------------- 15
PID - PID Controller Function Block
RG PTR - Range Pointer -_-------- Loop01.AIN1.OR
INPUT P - Input P ----------------- Loop01.AIN1.O1
INPUT S - Input S ----------------- Loop01.SPLIM.O1
INPUT F - Input F ----------------- Loop01.A/M.O1
INPUT A - Input A ---------------- Loop01.A/M.AS
ESN - Exec. Seq. No.-------------- 20
Содержание 353
Страница 12: ...Contents UM353 1B x April 2012 ...
Страница 22: ...Introduction UM353 1B April 2012 1 10 ...
Страница 30: ...Configuration Overview UM353 1B April 2012 2 8 ...
Страница 122: ...Function Blocks UM353 1B April 2012 3 92 ...
Страница 168: ...Data Mapping UM353 1B April 2012 6 28 ...
Страница 204: ...Controller and System Test UM353 1B April 2012 9 8 ...
Страница 222: ...Calibration UM353 1B April 2012 11 4 ...
Страница 226: ...Circuit Description UM353 1B April 2012 12 4 ...
Страница 238: ...Model Designation and Specifications UM353 1B April 2012 13 12 EC Declaration of Conformity ...
Страница 239: ...UM353 1B Model Designation and Specifications April 2012 13 13 Annex A to the EC Declaration of Conformity ...
Страница 240: ...Model Designation and Specifications UM353 1B April 2012 13 14 ...
Страница 244: ...Abbreviations And Acronyms UM353 1B 14 4 April 2012 ...