UM353-1B
Controller and System Test
April 2012
9-1
9.0 CONTROLLER AND SYSTEM TEST
This section presents a series of steps to verify controller operation and to help a user become familiar with the
functionality of the controller. A new controller is shipped factory configured with either Factory Configured
Option FCO101 Single Loop Controller or a user-specified custom configuration. The following procedure is for
FCO101 with factory set parameter values. If a custom configuration was installed, or if you have configured the
controller, it may be necessary to modify the procedure to test all function blocks in that configuration.
To determine the current configuration of a controller, either:
•
refer to your configuration documentation for that controller
•
upload the configuration to a PC running the Graphical Configuration Utility where the configuration can be
viewed
•
enter the configuration mode and step through the configuration recording the configured function blocks and
entered parameter values
In the following steps, ‘press’ indicates a faceplate button (key).
9.1 CONTROLLER CONFIGURATION AND TEST
The purpose of this section is to configure and test the controller and to familiarize the user with the controller’s
faceplate pushbuttons, pulser, and displays. This section also introduces several configuration topics.
9.1.1 Connections and Power
1.
Connect power to the controller. Refer to Controller nameplate for model number and then to Section 13
Model Designation and Specifications for power requirements. Refer to Section 7 Installation for connections.
WARNING
Electrical shock hazard
Explosion hazard
Can cause death or injury
•
Remove power from all wires and terminals before working on equipment.
•
In potentially hazardous atmosphere, remove power from equipment before
connecting or disconnecting power, signal, or other circuit.
•
Observe all pertinent regulations regarding installation in hazardous area.
2.
Depending upon the configuration, connect test equipment to the I/O terminals.
FCO101 - This FCO has one 1-5 Volt analog input (AIN1), and one 4-20 mA analog output (AOUT1)
configured. To verify both of these outputs, and to simulate an analog input for subsequent steps, jumper the
terminals shown below. Connect a 250 ohm range resistor across the terminals shown below to convert the 4-
20 mA output to a 1-5 volt input. This will tie the valve output (horizontal bargraph) back in the loop as the
process input (P bargraph). Refer to Section 7 Installation as necessary.
CONTROLLER JUMPER
TERMINAL
INSTALL 250
Ω
AT TERMINALS
Model 353
17 to 20
From 18 to 20
Custom Configuration - Refer to Section 7 Installation as necessary for any additional connections.
3.
Apply power to the controller. Refer to Section 10.3 Troubleshooting for the display sequence during start up,
while the controller performs power-up diagnostics.
Содержание 353
Страница 12: ...Contents UM353 1B x April 2012 ...
Страница 22: ...Introduction UM353 1B April 2012 1 10 ...
Страница 30: ...Configuration Overview UM353 1B April 2012 2 8 ...
Страница 122: ...Function Blocks UM353 1B April 2012 3 92 ...
Страница 168: ...Data Mapping UM353 1B April 2012 6 28 ...
Страница 204: ...Controller and System Test UM353 1B April 2012 9 8 ...
Страница 222: ...Calibration UM353 1B April 2012 11 4 ...
Страница 226: ...Circuit Description UM353 1B April 2012 12 4 ...
Страница 238: ...Model Designation and Specifications UM353 1B April 2012 13 12 EC Declaration of Conformity ...
Страница 239: ...UM353 1B Model Designation and Specifications April 2012 13 13 Annex A to the EC Declaration of Conformity ...
Страница 240: ...Model Designation and Specifications UM353 1B April 2012 13 14 ...
Страница 244: ...Abbreviations And Acronyms UM353 1B 14 4 April 2012 ...