2
SEL-700G Relay
Instruction Manual
Date Code 20170814
SEL-700G Relay Command Summary
FIL READ
filename
Transfers settings file
filename
from the relay to the PC.
FIL SHOW
filename
Displays contents of the file
filename
.
GEN
Displays generator operating statistics report.
GSH
Displays the generator autosynchronism report history.
GST
Triggers generator autosynchronism report data capture.
GOO
k
Displays transmit and receive GOOSE messaging information. Enter number
k
to scroll the GOOSE data
k
times on the screen.
GRO
Displays active group setting.
HEL
Displays a short description of selected commands.
HIS
n
Shows summary of
n
latest event reports, where
n
= 1 is the most recent entry. If
n
is not specified, all
event report summaries are displayed.
HIS C
or
R
Clears or resets history buffer.
IRIG
Forces synchronization of internal control clock to IRIG-B time-code input.
LDP
Displays signal profile data.
LDP C
Clears signal profile data.
MAC
Displays the MAC address of the Ethernet port (PORT 1).
MET
Displays instantaneous metering data.
MET
k
Displays instantaneous metering data
k
times, where
k
is between 1 and 32767.
MET AI
Displays analog input (transducer) data.
MET DEM
k
Displays demand metering data, in primary amperes. Enter
k
to scroll metering
k
times on screen.
MET
DIF
k
Displays differential metering data. Enter
k
to scroll metering
k
times on the screen.
MET E
Displays energy metering data.
MET
H
Displays harmonic report for all differential phase currents, showing fundamental through fifth harmonic
levels and total harmonic distortion (THD %).
MET M
Displays minimum and maximum metering data.
MET MV
Displays SEL
OGIC
math variable data.
MET PEA
k
Displays peak demand metering data, in primary amperes. Enter
k
to scroll metering k times on screen.
MET PM
Displays synchrophasor metering data.
MET RD
Resets demand metering values.
MET RE
Resets energy metering data.
MET RM
Resets minimum and maximum metering data.
MET RMS
Displays
rms metering data.
MET RP
Resets peak demand metering values.
MET T
Displays thermal capacity used and RTD metering data.
PING x.x.x.x t
Determines if Ethernet port is functioning or configured properly. x.x.x.x is the IP address and “t” is the
PING interval settable from 2 to 255 seconds. Default “t” is 1 second. Press Q to stop.
SER
Displays all Sequential Events Recorder (SER) data.
SER
d1
Displays all SER records made on date
d1
.
SER
d1 d2
Displays all SER records made from dates
d2
to
d1
, inclusive, starting with
d2
.
SER
n
Displays the
n
most recent SER records starting with record
n
.
SER
n1
n2
Displays SER records
n2
to
n1
, starting with
n2
.
Serial Port Command
Command Description
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...