A.5
Date Code 20170814
Instruction Manual
SEL-700G Relay
Firmware and Manual Versions
Firmware
➤
Corrected IEC 61850 KEMA compliance issue (Sisco library).
➤
Corrected issue of SALARM not asserting for a settings
group change.
➤
Corrected DNP polling issue with IN101.
➤
Corrected issue with reading Communications Counter reg-
isters (Registers 910–919) using the user map.
➤
Corrected issue with MMS error message in response to
IEC 61850 control operation failure.
➤
Corrected issue with RMS Meter values where in some
cases the values would spike for a short time.
➤
Corrected issue with Relay Word bit 46Q2R (reset for 46Q2
element) not resetting to state =1 when E46 is turned OFF.
➤
Corrected issue ( for IEC 61850 and DNP) of missing SER
records upon warm start.
➤
Corrected issue where METER displayed wrong informa-
tion for “LEAD” and “LAG” in QuickSet.
➤
Corrected primary current magnitude calculation for delta-
connected CTs by dividing by square root of 3 factor in the
meter and event report delta current quantities.
SEL-700G-R103-V0-Z001001-D20110324
➤
Corrected the issue with the analog quantities for real
power, reactive power, apparent power, and power factor
where those values became fixed at zero after power to the
relay was cycled.
➤
Corrected the issue with trip logic equations TR1, TR2, and
TR3 for the SEL-700GW and SEL-700GT models. These
equations were being processed instead of being disabled,
which affected the TRIP LED target.
➤
Corrected the issue (R102 only) with inverse time-overcur-
rent elements (did not accumulate time correctly for
FNOM = 50,Hz nominal frequency—times were about
20% faster).
➤
Corrected the issue with TCU alarm function when set to
OFF. The relay was still processing and issuing an alarm.
➤
Corrected the issue in R102 firmware with a settings
change from
AC
SEL
ERATOR
QuickSet SEL-5030 Software
or via terminal mode. When settings with E49RTD enabled
were downloaded, the relay became disabled and displayed
a VECTOR 40 message.
➤
Made the SEL-700 series Flash driver more robust to pre-
vent unintended writes or erasures.
20110324
SEL-700G-R102-V0-Z001001-D20101206
➤
Corrected LDP command issue (relay will lock up, vector,
or respond unpredictably if Load Data Profile (LDP)
records overflow the allotted storage space) in R100-101
firmware revisions.
➤
Corrected issue with inverse time-overcurrent elements.
(Did not accumulate time correctly at off-nominal frequency).
➤
Implemented improved diagnostics and actions in the relay
self-tests. For certain failures, the relay will automatically
restart as many as three times.
20101206
SEL-700G-R101-V0-Z001001-D20100521
➤
Implemented calibration improvements.
20100521
SEL-700G-R100-V0-Z001001-D20100416
➤
Initial version.
20100416
Table A.1
Firmware Revision History
(Sheet 5 of 5)
Firmware Identification (FID) Number
Summary of Revisions
Manual Date Code
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...