4.199
Date Code 20170814
Instruction Manual
SEL-700G Relay
Protection and Logic Functions
Logic Settings (SET L Command)
MV01 :=
12 * IN101 + (MV01 + 1) * NOT IN101
The previous equation sets MV01
to 12 whenever IN101 asserts. Otherwise, it increments MV01 by 1 each time
the equation is executed.
Boolean Rising-Edge Operator (R_TRIG)
Apply the rising-edge operator, R_TRIG, to individual Relay Word bits only;
you cannot apply R_TRIG to groups of elements within parentheses. When
any Relay Word bit asserts (going from logical 0 to logical 1), R_TRIG
interprets this logical 0 to logical 1 transition as a “rising edge” and asserts to
logical 1 for one processing interval.
For example, the Boolean SEL
OGIC
control equation event report generation
setting uses rising-edge operators:
ER :=
R_TRIG IN101 OR R_TRIG IN102
The rising-edge operators detect a
logical 0 to logical 1 transition each time either IN101 or IN102 asserts. Using
these settings, the device triggers a new event report each time IN101 or
IN102 asserts anew, if the device is not already recording an event report. You
can use the rising-edge operator with the NOT operator as long as the NOT
operator precedes the R_TRIG operator. The NOT R_TRIG combination
produces a logical 0 for one processing interval when it detects a rising edge
on the specified element.
Boolean Falling-Edge Operator (F_TRIG)
Apply the falling-edge operator, F_TRIG, to individual Relay Word bits only;
you cannot apply F_TRIG to groups of elements within parentheses. The
falling-edge operator, F_TRIG, operates similarly to the rising-edge operator,
but it operates on Relay Word bit deassertion (elements going from logical 1
to logical 0) instead of Relay Word bit assertion. When the Relay Word bit
deasserts, F_TRIG interprets this logical 1 to logical 0 transition as a “falling
edge” and asserts to logical 1 for one processing interval, as shown in
Figure 4.136.
Figure 4.136
Result of Falling-Edge Operator on a Deasserting Input
You can use the falling-edge operator with the NOT operator as long as the
NOT operator precedes the F_TRIG operator. The NOT F_TRIG combination
produces a logical 0 for one processing interval when it detects a falling edge
on the specified element.
Math Arithmetic Operators (*, /, +, and –)
If Relay Word bits (which are effectively Boolean resultants, equal to logical 1
or logical 0) are used in mathematical operations, they are treated as
numerical values 0 and 1, depending on if the Relay Word bit is equal to
logical 0 or logical 1, respectively.
F_TRIG IN101
IN101
Falling Edge
One Processing Interval
One Processing Interval
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...