SET.51
of 68
Date Code 20170814
Instruction Manual
SEL-700G Relay
SEL-700G Settings Sheets
SET PORT p (p = F, 1, 2, 3, or 4) Command
Port Number Settings Must be Unique
When making the SEL-700G Port 1 settings, port number settings cannot be used for more than one protocol. The
relay checks all of the settings shown in Table SET.1 before saving changes. If a port number is used more than
once, or if it matches any of the fixed port numbers (20, 21, 23, 102, 502), the relay displays an error message and
returns to the first setting that is in error or contains a duplicate value.
Make the following setting when ESNTP = UNICAST.
Backup Server IP Address (zzz.yyy.xxx.www)
SNTPBSIP :=
SNTP IP (Local) Port Number (1–65534)
SNTPPORT :=
Note: See Table SET.1 and the note at the end of Port 1 settings.
SNTP Update Rate (15–3600 seconds)
SNTPRATE: =
Make the following setting when ESNTP = UNICAST or MANYCAST.
SNTP Timeout (5–20 seconds)
SNTPTO : =
Note: SNTPTO must be less than setting SNTPRATE.
Table SET.1
Port Number Settings That Must be Unique
Setting
Name
Setting Required When
TPORT
Telnet Port
Always
MODNUM1
a
Modbus TCP Port 1
EMOD > 0
MODNUM2
Modbus TCP Port 2
EMOD > 1
PMOTCP1
PMU Output 1 TCP/IP (Local) Port Number
PMOTS1 = TCP, UDP_T, or UDP_U
PMOTCP2
PMU Output 2 TCP/IP (Local) Port Number
PMOTS2 = TCP, UDP_T, or UDP_U
DNPNUM
DNPTCP and UDP Port
EDNP > 0
SNTPPORT
SNTPIP (Local) Port Number
ESNTP
OFF
a
MODNUM1 and MODNUM2 can have the same port number. The relay displays an error message if this number matches with the port
numbers of the other protocols.
PORT 2
(Fiber-Optic Serial Port in Slot B; hidden if E49RTD := EXT)
PROTOCOL
(SEL, DNP, MOD, EVMSG, PMU, MBA, MBB, MB8A, MB8B, MBTA, MBTB)
PROTO :=
Communications
SPEED (300, 1200, 2400, 4800, 9600, 19200, 38400 bps)
SPEED :=
DATA BITS (7, 8 bits) (Hidden if PROTO := MOD, DNP, PMU, EVMSG, or MB_)
BITS :=
PARITY (O, E, N)
(Hidden if E49RTD := EXT or if PROTO := EVMSG, PMU, or MB_)
PARITY :=
STOP BITS (1, 2 bits) (Hidden if PROTO := MOD, EVMSG, or MB_)
STOP :=
PORT TIME-OUT (0–30 min) (Hidden if PROTO := MOD, PMU, EVMSG, or MB_)
T_OUT :=
SEND AUTOMESSAGE (Y, N)
(Hidden if PROTO := MOD, DNP, PMU, EVMSG, or MB_)
AUTO :=
FAST OP MESSAGES (Y, N)
(Hidden if PROTO := MOD, DNP, PMU, EVMSG, or MB_)
FASTOP :=
HDWR HANDSHAKING (Y, N)
(Hidden if PROTO := MOD, DNP, SEL, PMU, EVMSG, or MB_)
RTSCTS :=
Modbus
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...