J.17
Date Code 20170814
Instruction Manual
SEL-700G Relay
Relay Word Bits
Definitions
87SC3
Restrained High Security Differential Element 3 (not considering harmonic blocks)
152
87SN1
Restrained Sensitive Differential Element 1 (not considering harmonic blocks)
151
87SN2
Restrained Sensitive Differential Element 2 (not considering harmonic blocks)
151
87SN3
Restrained Sensitive Differential Element 3 (not considering harmonic blocks)
151
87U
Unrestrained differential element trip (87U1 OR 87U2 OR 87U3)
11
87U1
Unrestrained Differential Element 1 trip
11
87U2
Unrestrained Differential Element 2 trip
11
87U3
Unrestrained Differential Element 3 trip
11
AI301HAL–AI504HAL
Analog inputs 301–504 warnings/alarms (where xxx = 301–504) high alarm limit
120–131
AI301HW1–AI504HW1 Analog inputs 301–504 warnings/alarms (where xxx = 301–504) high warning, Level 1
120–131
AI301HW2–AI504HW2 Analog inputs 301–504 warnings/alarms (where xxx = 301–504) high warning, Level 2
120–131
AI301LAL–AI504LAL
Analog inputs 301–504 warnings/alarms (where xxx = 301–504) low alarm limit
120–131
AI301LW1–AI504LW1
Analog inputs 301–504 warnings/alarms (where xxx = 301–504) low warning, Level 1
120–131
AI301LW2–AI504LW2
Analog inputs 301–504 warnings/alarms (where xxx = 301–504) low warning, Level 2
120–131
AIHAL
Analog inputs high alarm limit, if any AIxxxHAL = 1, then AIHAL = 1
119
AIHW1
Analog inputs high warning, Level 1, if any AIxxxHW1 = 1, then AIHW1 = 1
119
AIHW2
Analog inputs high warning, Level 2, if any AIxxxHW2 = 1, then AIHW2 = 1
119
AILAL
Analog inputs low alarm limit, if any AIxxxLAL = 1, then AILAL = 1
119
AILW1
Analog inputs low warning, Level 1, if any AIxxxLW1 = 1, then AILW1 = 1
119
AILW2
Analog inputs low warning, Level 2, if any AIxxxLW2 = 1, then AILW2 = 1
119
AMBALRM
Ambient temperature alarm. AMBALRM asserts if the healthy ambient RTD temperature
exceeds its alarm set point.
44
AMBTRIP
Ambient Temperature trip. AMBTRIP asserts when the healthy Ambient RTD
temperature exceeds its trip set point.
44
ASP
Autosynchronism stop
42
AST
Autosynchronism start
40
ASYNSDC
Asynchronous sampling data conversion is in process
62
BCWAX
X-side breaker A-phase breaker contact wear has reached 100 percent wear level
63
BCWAY
Y-side breaker A-phase breaker contact wear has reached 100 percent wear level
63
BCWBX
X-side breaker B-phase breaker contact wear has reached 100 percent wear level
63
BCWBY
Y-side breaker B-phase breaker contact wear has reached 100 percent wear level
63
BCWBY
Y-side breaker C-phase breaker contact wear has reached 100 percent wear level
63
BCWCX
X-side breaker C-phase breaker contact wear has reached 100 percent wear level
63
BCWX
BCWX = BCWAX OR BCWBX OR BCWCX
63
BCWY
BCWY = BCWAY OR BCWBY OR BCWCY
63
Table J.3
Relay Word Bit Definitions for the SEL-700G
(Sheet 11 of 22)
Bit
Definition
Row
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...