4.223
Date Code 20170814
Instruction Manual
SEL-700G Relay
Protection and Logic Functions
Front-Panel Settings (SET F Command)
Appendix C: SEL Communications Processors for the description of the
SEL-700G Fast Operate commands.
Set PROTO := DNET to establish communications when the DeviceNet card
is used. Table 4.80 shows the additional settings, which can be set only at the
rear on the DeviceNet card. Once the relay detects the DeviceNet card, all
Port 4
settings are hidden. Refer to Appendix G: DeviceNet Communications
for details on DeviceNet.
Front-Panel Settings (SET F Command)
General Settings
Local bits provide control from the front panel (local bits), and display points
display selected information on the LCD display. However, you need to first
enable the appropriate number of local bits and display points necessary for
your application. When your SEL-700G arrives, two display points are
already enabled, but no local bits are enabled. If more display points are
necessary for your application, use the EDP setting to enable as many as 32
display points. Use the ELB setting to enable as many as 32 local bits.
To optimize the time you spend on setting the device, the relay makes only the
number of enabled display points and enabled local bits available for use. Use
the front-panel LCD timeout setting FP_TO as a security measure. If the
display is within an Access Level 2 function, such as the device setting entry,
when a timeout occurs, the function is automatically terminated (without
saving changes) after inactivity for this length of time. After terminating the
function, the front-panel display returns to the default display. If you prefer to
disable the front-panel timeout function during device testing, set the LCD
timeout equal to OFF. Use the front-panel LCD contrast setting FP_CONT to
adjust the contrast of the liquid crystal display. Use the front-panel auto-
message setting FP_AUTO to define displaying of the trip/warning messages.
Set FP_AUTO either to Override or add to the Rotating display when the relay
triggers a trip/warning message. Set RSTLED := Y to reset the latched LEDs
automatically when the breaker or contactor closes.
Table 4.80
Rear-Panel DeviceNet Port Settings
Setting Name
Setting Range
MAC_ID
0–63
ASA
8 Hex characters assigned by factory
DN_Rate
125, 250, 500 kbps
Table 4.81
Display Point and Local Bit Default Settings
Setting
Setting Prompt
Range
Default
EDP
DISPLAY PTS ENABL
N, 1–32
2
ELB
LOCAL BITS ENABL
N, 1–32
N
Table 4.82
LCD Display Settings
Setting
Setting Prompt
Range
Default
FP_TO
LCD TIMEOUT
OFF, 1–30; min
15
FP_CONT
LCD CONTRAST
1–8
5
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...