D.27
Date Code 20170814
Instruction Manual
SEL-700G Relay
DNP3 Communications
DNP3 Documentation
To set these points as part of custom map 1, you can use the SET DNP 1
AI_00 TERSE <Enter> command as shown in Figure D.5.
You can also use QuickSet to enter the previous AI map settings as shown in
the screen capture in Figure D.6. You can enter scaling and dead-band settings
in the same pop-up dialog used to select the AI point, as shown in Figure D.7.
6
X-Side AB Phase-to-Phase
Voltage Angle
VABX_ANG
1
15
7
X-Side Frequency
FREQX
.01
1
=>>
SET DNP 1 AI_00 TERSE <Enter>
Analog Input Map
DNP Analog Input Label Name (25 characters)
AI_00 := NA
? >
IAX_MAG <Enter>
AI_01 := NA
? >
IBX_MAG <Enter>
AI_02 := NA
? >
ICX_MAG <Enter>
AI_03 := NA
? >
IAY_MAG <Enter>
AI_04 := NA
? >
P3X:5 <Enter>
AI_05 := NA
? >
VAX_MAG <Enter>
AI_06 := NA
? >
VAX_ANG:1:15 <Enter>
AI_07 := NA
? >
FREQX:.01:1 <Enter>
AI_08 := NA
? >
end <Enter>
Save changes (Y/N) ?
Y <Enter>
=>>
Figure D.5
Sample Custom DNP3 AI Map Settings
Table D.13
Sample Custom DNP3 AI Map
(Sheet 2 of 2)
Desired
Point
Index
Description
Label
Scaling
Dead
Band
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...